Honeywell
Honeywell FSL100 Flame Detector
Model No :
Honeywell- FSL-100
Part Code :
FSL-100

Overview

FSL100 Flame Detectors with simple installation, set-up and operation enables simple coverage of fire hazard areas across many fire hazard applications. FSL-100 detects wide range of Hydrocarbon & Non-Hydrocarbon fires. It has Wide viewing angle, Fast response and can be installed indoors or outdoors and in Hazardous areas typically looking into a Zone 1 area from a distance.

Features
- UV, UV/IR and IR3 Flame Detectors to cover a wide range of applications
- Robust, simple to install & set-up; Wide angle and fast speed of response
- Automatic test and test lamps for simple check and maintenance

Major Applications
- Offshore oil & gas terminals
- LPG storage areas
- Cold storege
- Diesel engine rooms
- Fume hoods
- Paint spray booths

Technical Specifications
- FSL100 Flame Detector types FSL100-UV, FSL100-UVIR and FSL100-IR3; Choice of red or white housings
- Range 110 ft /35 m (IR3), 25 m/80 ft (UV, UV/IR) alarming within 10 seconds to a 1 ft2(0.1 m2)n-heptane fire
- Cone of vision 90°minimum horizontal and vertical
- Power 10-28 VDC (12-24 VDC nominal)
-Local LEDs:
• Continuous green: normal operation
• Continuous yellow: fault
• Flashing yellow: Fault and guide to repeat self-test after a self-test failure
• Continuous red: alarm
- Start up times :- <10 sec
- Alarm response time : 8 to 30 sec
- Alarm output settings : Selectable LEDs and relays latching/non-latching; factory setting: latching
- Automatic & manual Self-Test : Automatic Sensor Test (built in Self-Test) and manual Self-Test

General Specifications
- Dimensions :- 4.9 x 3.15 x 2.25 in (125 x 80 x 57 mm)
- Weight :- 1.05 lb (465 g)
- Ingress protection :- IP65
- Temperature, operating :- –40 °F to +158 °F (–40 °C to +70 °C)
- Temperature, ambient ATEX and FM class 3611 :- –13 °F to +158 °F (–25 °C to +70 °C)